The 501/453/Universal Cable Gland is a Group II certified double seal cable gland suitable for installation in Zone 1/21 and Zone 2/22 hazardous areas. Dual Certified ATEX/IECEx (along with many more) for use in Increased Safety (Exe), Flameproof (Exd), Restricted Breathing (ExnR) and Dust (Ext) protection concepts. Integral grounding ring suitable for single wire armour ‘W’, wire braid ‘X’ and tape armour ‘Z’. Suitable for both elastomer and plastic insulated cables, and particularly for cables which exhibit 'cold flow' characteristics on the inner sheath. The gland also provides an elastomeric seal on the cable inner sheath, and a low smoke, zero halogen IP and retention seal onto the cable outer sheath.
- Metallic body construction
- Elastomeric Exd passive diaphragm seal on cable inner sheath - helping to eliminate cold flow and fully inspectable in situ
- Reversible Armour Clamp - For all types of armour, braid and tape
- Patented Cable Gland Tightening Guide - Helps prevent damage caused by over tightening
- Unique Rear Seal - Offering ultimate sealing over an extremely wide cable acceptance range
- Inspectable Deluge Seal - Offering IP66, IP67, IP68 & IP69 Ingress Protection
- Available with metric or NPT entry threadforms
Specifications
Application
|
Hazardous Areas Zone 1, Zone 21, Zone 2, Zone 22 |
Ingress Protection |
- IP66, IP67 IP68 (30 metres for 7 days, special conditions may apply) and IP69 to IEC/EN 60529
- NEMA 4X
- Deluge Protection to DTS01
|
Material |
Manufactured in Brass, Nickel Plated Brass or 316L Stainless Steel |
Operating Temperature |
-60°C to +80 °C |
Series |
Cable Glands for Group II Hazardous Areas |
More Data